A.4 Fisher Rosemount Provox    

Available in File and Simulink mode. The input and output signals should be measured in percentages (not in physical units).

A.4.1 Controller Template     


  
Figure A.14: Fisher Rosemount Provox Controller Template.
\begin{figure}
\centering
\includegraphics [width=11cm]{line1.ps}
\end{figure}


Standard sampling time is 1 sec. In File and Simulink mode, any sampling time can be entered. The template's parameter is (Figure A.14):

Control Action:
Reverse or Direct. Reverse mode for standard behavior (negative control action when the process output increases), direct action otherwise (positive control action when the process output increases).

A.4.2 Controller Parameters     


  
Figure A.15: Fisher Rosemount Provox Controller Edit window.
\begin{figure}
\centering
\includegraphics [width=11.6cm]{line1.ps}
\end{figure}


The complexity of the formula shown on top of the ``Edit Controller'' window (Figure A.15) depends on the structure selected in the ``Controller Structure'' window (Figure 6.5). The parameters are (Figure A.15):

Proportional Gain (K):
between 0.0 and 128.0.
Integral Time (Ti):
between 0.1 and 293.0 minutes. Equal to zero when there is no integral action in the controller.
Derivative Time (Td):
between 0.0 and 895.0 minutes. Equal to zero when there is no derivative action in the controller.
Manual Reset (Mr):
between 0.00 and 100.00 percent.
Gain Factor (gamma):
This factor is determined by the ``Control Action'' entered in the Template.
Control Action:
``Control Action'' as was entered in the Template.