2.6 Re-designing the controller  

Now that you have designed your first RaPID controller, you will refine it and try out different controllers. In this section, you first re-identify the model from closed loop measured data. Then you re-design a number of different controllers.

2.6.1 Identification from closed loop data       

In some cases it is very hard or even impossible to do an open loop experiment as in Section 2.2. Closed loop experiments however, are almost always within the range of possibilities. With the data of such a closed loop experiment (Figure 2.15), you can just as well identify the open loop linear model. Hit the identification button in the ``Closed Loop Data Acquisition'' window of Figure 2.15. The ``Identification'' window pops up with the ``PreProcessing'' window on top of it. Hit the ``OK'' button, and RaPID computes a model for you. The identified model has a delay of 1 second, one pole and no zero (the error is 1.6 %).

At this point, when you are not really sure about the model structure you have to select, you can resort to a parameter sweep (see also Section 5.7). Select the menu Identification $\rightarrow \;$Parameter Sweep or hit the ``Identification'' box in the configuration window. The ``Identification Parameter Sweep'' window pops up. This window allows you to compute a whole batch of models with different structures. Hit the ``Start'' button at the lower left corner, and watch how easy it is to compute 42 different models. The resulting window is displayed in Figure 2.16.


  
Figure 2.16: Resulting ``Identification Parameter Sweep'' window. The 42 identified models are ordered according to descending error. You should select the one with the lowest error and complexity.
\begin{figure}
\centering
\includegraphics [width=7.9cm]{line1.ps}
\end{figure}


After the computation of all models, the identification errors for the selected structures are displayed. When moving the mouse over the bar graph, the corresponding structure is displayed in the top right of the window. You should select the structure with the lowest complexity (The complexity is the sum of number of poles and zeros. A delay does not count.) and a small error. You can find this structure by moving the mouse from the right to the left over the plot. The structure with the lowest error (the one on the far right side) is 0.5/2/2 (indicating a delay of 0.5 seconds, two poles and two zeros). However, moving to the left with the mouse, you see that the structure 1/1/0 has a very comparable error but a lower complexity (less parameters). Select this structure (click with the left mouse button) and hit the export button (lower left of the window). The new model is computed and displayed in the main ``Identification'' window.

2.6.2 Some other controller designs

Now turn your attention again to the ``Controller Design'' window (hit the ``Controller'' button in the task bar or use the menu RaPID $\rightarrow \;$Control Design). Hit ``OK'' in the ``Control Design Parameters'' and the ``Design Reference Definition'' window.

Pre-designs    

Select the menu entry Controller $\rightarrow \;$Pre Design (see Section 6.5). This pops up the ``Pre Design'' window of Figure 2.17. Select the ``Fast Chien Hrones Reswick'' pre-design rule and look at the resulting signals in the main ``Control Design'' window. Clearly the tuning rule does not deliver satisfactory results (this is due to the large delay in the system). Note that the previous design is also plotted as a dotted line. This allows for an easy comparison between the current and previously designed controller. Try out some other tuning rules and find that many of them compute non-stabilizing controllers.


  
Figure 2.17: The ``Pre Design'' window contains a whole range of classical tuning rules. Some RaPID pre-designs are also listed.
\begin{figure}
\centering
\includegraphics [width=8cm]{line1.ps}
\end{figure}


Since this controller performance is clearly not satisfactory, you should return to the RaPID designs. Close the ``PreDesign'' window and hit the ``RaPID'' button which appears in the main ``Control Design'' window (on top of the plots).

Controller Structure    

Now you will change the controller structure. Open the ``Controller Structure'' window from the menu Controller $\rightarrow \;$Structure or by hitting the ``Controller'' box in the configuration plot of the ``Control Design'' window (see also Section 6.2.2). Figure 2.18 shows how the ``Throttle'' is computed on the basis of the ``Reference Speed'' and the ``Measured Speed''. The standard selection is a controller with an ``Integral (I)'' term working on the ``Error'' (the middle box in Figure 2.18), a ``Proportional (P)'' term working on the ``Reference Speed'' and the ``Measured Speed'' (the two proportional terms are different though) and a ``Derivative (D)'' term on the ``Measured Speed'' only. If needed, you can now change this structure. For instance, if you want the PID to act purely on the ``Error'', you should select in the middle box ``PID'', and a ``0'' in the ``Feedback'' and ``Feedforward'' box (as in Figure 2.19).


  
Figure 2.18: The ``Controller Structure'' window as it pops up the first time.
\begin{figure}
\centering
\includegraphics [width=12cm]{line1.ps}
\end{figure}



  
Figure 2.19: The ``Controller Structure'' window after modification to a PID acting on the error only. Most industrial controllers fit into this general structure window.
\begin{figure}
\centering
\includegraphics [width=12cm]{line1.ps}
\end{figure}


Hit the ``OK'' button in the ``Controller Structure'' window. The new controller is automatically computed. When you inspect the signals in the main ``Control Design'' window, you will note that there is not much difference between the two controllers with the different structures (compare the full lines with the dotted lines).

In a similar way, the controller structure can be reduced to a ``PI'' or ``PD'' controller. You can even include a ``Double Derivative'' term, which is very useful when controlling integrating processes. See Section 6.2.2 and the RaPID course notes for more details.

Controller Parameters   

Finally, you can fine tune the controller with the design parameters ``Robustness'' and ``HF Gain'' in the main ``Control Design'' window. The meaning of these parameters is roughly as follows: the ``Robustness'' is related to the gain and phase margins of the controlled system. A high robustness implies a higher guaranteed gain and phase margin and vice versa (see Section 6.3.3 and Table 6.3). The ``HF Gain'' which is short for ``high frequency controller gain'', stands for the sensitivity of the process input to measurement noise. Roughly, it means that a disturbance signal with amplitude 1 added to the ``Speed'' will be amplified with a factor ``HF Gain'' towards the ``Throttle''. So, a high ``HF Gain'' implies a high noise sensitivity and vice versa (see Section 6.3.3).     

Often, there are specifications given that determine one or both parameters. If not, you can play around with them, until you find a good solution. Alternatively, just as for the identification parameters, you can apply a parameter sweep. Select the menu Controller $\rightarrow \;$Parameter Sweep to start the ``Controller Parameter Sweep'' window. Then select a ``Robustness'' range from 55 % to 80 % in 6 intervals and a ``HF Gain'' range from 2 to 20 in 3 intervals. Hit the ``Start'' button. 18 different controllers are now computed, and ordered towards descending settling time (since you originally specified that the settling time should be optimized in the ``Control Design Parameters'' window of Figure 2.11). This results in Figure 2.20.


  
Figure 2.20: The ``Controller Parameter Sweep'' window from which you can easily determine the optimal controller parameters ``Robustness'' and ``HF Gain'' that minimize your controller performance index (the settling time for this example).
\begin{figure}
\centering
\includegraphics [width=8.4cm]{line1.ps}
\end{figure}


Now select the most right bar in the plot by clicking on it, and hit the export button. The new controller is computed and displayed in the main ``Controller Design'' window. It clearly has a shorter settling time than the previously designed controller.