As a thermal example, you will design a controller for a
superheater in a thermo-electrical power plant. Start RaPID in
Simulink mode and load the demo project ``Superheater in a
thermo-electrical power plant'' through the file menu File
Demo
Projects. When you load the demo project, not only the project is
loaded, but also a good input excitation signal. Figure
8.13 shows the main ``Data Acquisition'' window after
the project was loaded.
The superheater is a part of a thermo-electrical power plant. It is located right before a high pressure steam turbine. Overheated steam (300 ton/hour) enters the superheater at 120 bar and minimum 450 degrees Celsius. In the superheater the temperature is raised to 484.7 degrees. The superheater is modeled as a counterflow tube-in-tube heat exchanger, where heat is exchanged between exhaust gases (mainly CO2) and the overheated steam. It is very important to have a constant temperature of 484.7 degrees at the outlet of the superheater because:
Therefore, the temperature has to be controlled. This is done through the injection of water right before the steam enters the superheater. The amount of injected water (at 20 degrees) is controlled by a valve, the position of which (between 0 and 100 %) is denoted with IVP (``Implied Valve Position'').
In steady state an IVP value of 40 % corresponds to a 484.7 degrees Celsius outlet. The signals are sampled with a sampling time of 0.5 minutes (2 samples per minute). Typical disturbances that have to be controlled can be translated into load disturbances of approximately 10 % at the input.
Have a look at the process by opening the Simulink model with the
menu Simulink
Model, or by editing the project with the menu Edit
Project. Inspect the parameter file with the menu Simulink
Parameter File and the text file with Simulink
Text File.
The data acquisition is simply started by hitting the ``Start'' button in the acquisition window. The step input from 40 to 60 % is applied to the valve. More cold water is injected and the temperature thus drops from 484.7 to approximately 479 degrees. This implies a negative DC gain of 0.3 degrees/percent.
From the step response, you find a reasonably large time delay.
A crude inspection indicates 6 to 12 minutes. Zooming in on the
temperature at the tail, reveals a noise level amplitude on the output
temperature of approximately
0.6 degrees. You will use this
information during the control design.
Hit the identification button to switch to the ``Identification'' window. In the ``PreProcessing'' window (Figure 8.14) choose the whole data record. Choose a process output working point of 484.7 degrees and a process input working point of 40 %. There is no integrator present and there is no need to filter the data. Figure 8.14 shows the resulting ``PreProcessing'' window.
Hit the ``OK'' button in the ``PreProcessing'' window. The model is automatically computed and the signals displayed. Figure 8.15 shows the resulting ``Identification'' window. The resulting default model is reasonably good (14.4 % error). The ``Negative DC gain'' warning in the message area (bottom right of Figure 8.15) was to be expected (you found a negative gain during the open loop data acquisition).
You will now improve on the identified model. First, you should
increase the range of possible delays (the maximal delay that can be
chosen in Figure 8.15 is only 7 minutes, while you
expect a delay of up to 12 minutes). Open the ``Identification
Settings'' window with the menu entry Identification
Settings and
change the ``Maximal Delay'' to 12 minutes. Hit ``OK''.
Now you can find a good model by applying a parameter sweep.
Open the ``Identification Parameter Sweep'' window by hitting the
``Identification'' box in the configuration window or from the menu
Identification
Parameter Sweep. You know the delay to be between
6 and 12 minutes. The number of poles could be 1 or 2 and the
number of zeros could be between 0 and 2. Figure
8.16 shows the resulting parameter sweep. Looking
for a good model with a low complexity, you end up at the 9/2/0
model (it is the first model from the right with no zeros). Click the
model bar and ``Export'' the model. The resulting model error is
13.7 % and the predicted temperature is close to the measured
temperature.
Inspection of the ``Model Numerics'' (Figure
8.17) shows a DC gain of -0.29
degrees/percent and
a double time constant at 9 minutes. The ``Model Properties''
window reveals a rise time of 44 minutes and settling time of 61
minutes.
You are now ready to start the Control Design for the superheater. Hit the ``Controller'' button in the task bar to switch to the ``Control Design'' window. The ``Control Design Parameter'' window pops up. As introduced before, the controller should reject load disturbances of about 10 % as good as possible. You should thus select ``Variance and Tracking'' as ``Controller Type'' and ``Load'' as ``Origin''. Hit the ``OK'' button in the ``Control Design Parameters'' window.
The ``Design Load Definition'' window, which is the next window popping up, allows you to define the load signal shape. A step load of ``Amplitude'' 10 % should be entered. Hitting the ``OK'' button starts the computation of the controller. The resulting ``Controller Design'' window is shown in Figure 8.18.
The top plot of Figure 8.18 shows the constant
reference signal at 484.7 degrees and the output due to a load
disturbance. The bottom signal shows the ``implied valve position''
and the load disturbance. The controller has a robustness of 65 %,
which is translated into a gain margin of 9.4 dB and a phase margin
of 61 degrees (View
Loop Numerics). The ``HF Gain'' is 4
percent/degree, which implies that the noise of amplitude 0.6
degrees will be amplified with a factor 4 to and amplitude of 2.5
percent on the valve. This is acceptable for this application.
Say, you have to implement the controller on a DCS system
Honeywell TDC 3000. To load the specified template, hit the
``Controller'' box in the configuration window (or use the menu
Controller
Structure). Then, hit the template button at the lower
left corner. The ``Controller Template'' window of Figure
8.19 pops up. Select ``Distributed Control Systems''
from the pop up menu, and then select Honeywell TDC 3000 from the
list. In the ``Parameter'' list you should also change the ``Control
Action'' from ``Reverse'' to ``Direct'' since the process at hand has
a negative gain. Do not store this template as the default
one.
Hit the ``OK'' buttons in the ``Controller Template'' window and
in the ``Controller Structure'' window. The controller is
automatically recomputed within the structure of the TDC 3000. Note
that there is hardly any difference between the original and new
controller. Selecting the menu entry Edit
Controller pops up
Figure 8.20. which contains all information in a
form accepted by the TDC 3000. Note that the derivative time Td is
very small, and the controller thus almost corresponds to a PI
controller.
As a final step, save this designed controller as a benchmark
controller using Edit
Designed
Benchmark Controller.
Now you are ready to test the controller in practice. Hit the ``Closed Loop'' button in the task bar, resulting in the ``Closed Loop Data Acquisition'' window. The reference is drawn as a blue line, while the simulation is yellow dotted. For this example, the reference is constant and the simulation too. Unfortunately, it is not possible to include the step load in the simulation (You could alter the Simulink model to include the load step.) so we will just look at the behavior of the controller under noise.
Hit the ``Start'' button to start the Simulink experiment. The
result is shown in Figure 8.21. Select View
Analysis to have a look at the standard deviations of the signal. The
window displays 0.305 degrees for the standard deviation of the
temperature at the output and 1.04 percent for the standard
deviation of the IVP. This corresponds to 3.4 percent/degree, which
is close to the Control Design ``HF Gain'' 4 percent/degree.
Save the measured data as benchmark data with the menu Edit
Measured
Benchmark Data.
Finally you will check what the classical tuning rules would have
done for you in this example. Select Controller
Pre Design to pop
up the ``Pre Design'' window. First select ``the classical rule of
Ziegler Nichols''. The rejection of the load is slower, but the
lowest attained temperature 483.2 degrees (use data viewing) is not
as deep as with the RaPID design 482.8 degrees (which should be your
benchmark design).
However, look at the design parameters, and note a
``Robustness'' of 60 % which is still fine (compare to 65 % for
the RaPID design) and a ``HF Gain'' of 109 percent/degree. This
indicates an extremely high noise sensitivity. This can be checked by
switching to the ``Closed Loop Data Acquisition'' window and running
the controller. The IVP goes completely out of range for this
controller. So even though the load rejection may look fine at first
sight, the controller itself is completely unacceptable in practice
(due to the high noise sensitivity). The IVP now has a standard
deviation of 23 versus an output noise level of 0.79 (use View
Analysis). Note that the temperature is very badly controlled because
the large excursions of the IVP excite the non-linear behavior of the
Simulink model.
Finally, you could try one of the better pre design rules in the ``Control Design'' window. For instance, a ``Fast Kappa Tau'' rule, which gives a reasonable load rejection. However, once again, the ``HF Gain'' is way too high, which again implies too much noise sensitivity. You can check this again in the ``Closed Loop Data Acquisition'' window. Figure 8.22 shows an overview of the standard deviations.