In the next two chapters we will explain how to hook some industrial controllers to RaPID. In this chapter we will treat the OMRON E5CK digital controller. The next chapter is about the Bailey Fisher & Porter 53Sl6000 digital controller.
It is important to consult the manual of the digital controller first before it is connected to the PC running RaPID.
Before the OMRON E5CK digital controller can be used with RAPID it is necessary that the controller is fully configured. This can be done manually by the push buttons or by appropriate software delivered by OMRON (see OMRON manual cat. No. H078-E1-2B). The user is free to configure most of the controller parameters as he wants. Some parameters must be set specific for the use with RAPID. These are:
Notice that these parameters may not be changed during the RaPID sessions. It takes to much time for RaPID to check if some parameters where adapted during the session. RaPID therefore assumes that, once the parameters are set, they are not changed anymore.
The OMRON digital controller must be connected to the PC as pointed out in Chapter 6 of the OMRON manual.
Now RAPID can start communicating with the OMRON controller if
the serial port base address of
the computer is known by RAPID. This address must be given to the
RAPID configuration program. These values can be found in Windows 95
under (My Computer
Control Panel
System
properties
Device Manager
Ports
Communication port 1 (2)
Properties
Resources . Typical values of the base address are
given in table 3.1
| Port number | Base Address |
| Com Port 1 | 03f8 hex |
| Com Port 2 | 02f8 hex |
Rapid only changes the following parameters in the OMRON E5CK:
| Parameter name | setting |
| Communication stop bits | 1 |
| Communication data length | 7 |
| Communication parity | even |
| Communication baud rate | 19200 |
| Communication unit No. |
All other parameters must be set by the user. The important parameters that are needed by RAPID to calculate the gains and the scaling parameters of the controller are retrieved by RAPID from the controller. See Appendix A of the user manual for more information about these parameters.
Note that the
parameter, which is used for
advanced PID control is put default to 0.65 by OMRON. The on board
auto tuners of OMRON do not manipulate this parameter. RAPID changes
this parameter also to set the optimal control parameters. The
parameter can however only be changed in the expansion mode of the OMRON E5CK.
Returning from the expansion mode to the normal operation
mode can only be done via a reset of the digital controller. So every time
the
parameter is changed the controller is reset. This can not be avoided
and the user should first take the consequences of this resetting into
account. During the reset time the controller does not control the
plant.
Since RAPID must retrieve the process value and the control output from the controller every sample time and send the desired setpoint and control parameters, a lot of serial port communication is needed between the PC and digital controller. since the maximum baud rate of the communication is limited to 19200 Baud the real time part of RAPID takes a lot of CPU resources from the PC although it mainly waits for the digital controller to respond via the serial communication. The sampling rate of the OMRON E5CK is fixed to 4 Hz for temperature inputs and 10 Hz for voltage or current inputs. A pentium 133 can easily communicate at 4 Hz with the digital controller such that there is enough time left for windows to manipulate the mouse signals and respond to the mouse button clicks. At 10 Hz however there are almost no resources left on the PC. It is therefore wise to define a 4 Hz, or slower, sample rate within the RAPID environment. The controller itself will still work at 4 or 10 Hz. This sub sampling is in practice always needed since the processes that are controlled by this type controller are generally very slow.