Before the BF&P 53SL6000 controller can be used with RAPID it is necessary that the controller is fully configured. This can be done manually by the push buttons or by appropriate software delivered by Bailey Fisher & Porter. The user is free to configure most of the controller parameters as he wants. Some parameters must be set specific for the use with RAPID. These are:
Rapid only changes the following parameters in the Bailey Fisher & Porter 53SL6000:
| Parameter name | setting |
| Communication stop bits | 1 |
| Communication data length | 7 |
| Communication parity | even |
| Communication baud rate | 28800 |
| Communication unit No. |
We refer to the manual of this digital controller for more information about these parameters. All other parameters must be set by the user. The important parameters that are needed by RAPID to calculate the gains and the scaling parameters of the controller are retrieved by RAPID from the controller. We refer to appendix A of the RaPID user manual for more information about these parameters.
The Bailey Fisher & Porter has 2 PID modules on board. This controller can therefore in a single loop mode (only 1 PID module is used) or in cascade mode (both PID modules are put in cascade). Since RaPID performs open- and closed loop experiments with these modules, it is necessary to configure the controller for open- and closed loop mode.
A scheme of the control algorithm for single loop mode is shown in Figures 4.1 and 4.2 and for cascade control in Figures 4.3 through 4.6. On this schemes it is also shown which parameters are set by RaPID and which are retrieved by RAPID. The setpoints are send by RAPID to the appropriate registers of the controller. It has no use connecting setpoint signals to the remote setpoint input of the controllers. These signals are not send to the PID blocks anyway. RAPID uses the STV (setpoint tracking value) register for controller 1 to set the setpoint for this controller and the setpoint push button register of controller 2, since the STV register does not exist for controller 2 in the 53SL6000.
Note that the setpoint slew rates are not a part of the RAPID model of the controller although they are located between the STV register and the control block (see Figures 4.1 through 4.6). These slew rates are therefore shut off by RaPID. RaPID has the possibilities to send smooth setpoints to the controller if needed without using the build in slew rate blocks. The output slew rates are located behind the OTV register (see Figures 4.1 through 4.6). If these slew rates are not put to zero by the user, RaPID will see this slew rate block as a part of the system to control. The user is advised to put this term to zero, but if necessary it can be put to other values.
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
For open loop experiments the OTV (output tracking value) register is used for controller 1. Since this register does not exist for controller 2 the open loop experiments are performed by changing the setpoint of controller 1. These register values are send to the process after they passed the output slew rate block. Rapid will try to identify these slew rate blocks as part of the model if they are not shut off.
Direct and reverse operation is set by the user in the controller by the push button menu's or by the Loopmaster program. Rapid will investigate the controller to see which option was chosen by the user.
General purpose registers ai7 and ai8 are used by RAPID for the Feedforward (ai7) and output tracking value of controller 1 (ai8). They may not be used for other purposes. The user can configure these register as mentioned above with the aid of the loopmaster program, but it is not necessary since RAPID makes those connections also in the digital controller during the initialization phase..
The sample rate of the controller is 20 Hz. As the communication baud rate is 28800 Baud, RAPID is capable of sending and receiving all the parameters at this rate. It is however common practice with those controller to do a down sampling within RAPID. Processes connected to the BF&P 53SL6000 controller are slow processes with time constant slower than 1 second.